This digital input module captures discrete signals for FUJI MICREX-SX automation systems. It interfaces directly with field sensors such as limit switches and proximity detectors. Therefore, it enables reliable status monitoring for industrial machine control applications.
Physical and Input Specifications
The FUJI NP1X6406-W measures 13.0 cm in length and 9.5 cm in width. Moreover, its module weight equals approximately 0.28 kg for DIN rail mounting. A single 20-pin removable terminal block handles all field wiring connections. Additionally, this module contains sixteen independent digital input channels.
| Parameter | Specification |
|---|---|
| Brand | FUJI Electric |
| Full Model | NP1X6406-W |
| Category | Digital Input Module |
| Dimensions (L x W x H) | 13.0 cm x 9.5 cm x 6.0 cm (5.12″ x 3.74″ x 2.36″) |
| Module Weight | 0.28 kg (0.62 lbs) |
| Primary Interface | 1 x 20-pin Removable Screw Terminal Block |
| Backplane Interface | 1 x 48-pin Male Connector (MICREX-SX Rack) |
| Operating Voltage | 24 VDC from Backplane (19.2 to 28.8 VDC) |
| Power Consumption | 2.0 W (Typical) |
| Input Channels | 16 Independent Channels |
| Input Type | Sink/Source (Selectable per Common Group) |
| Input Voltage Range | 0 to 30 VDC |
| Input On-State Voltage | > 15 VDC |
| Input Off-State Voltage | < 5 VDC |
| Input On-State Current | 7 mA Typical at 24 VDC |
| Input Impedance | 3.4 kΩ |
| Input Response Time (On) | 3 ms (Typical) |
| Input Response Time (Off) | 3 ms (Typical) |
| Input Isolation | Optocoupler (1500 Vrms) |
| Common Configuration | 16 Inputs Share Two Commons (8 per Group) |
| On-Board Components | 16 Optocouplers + 16 Current Limiting Resistors + 4 Protection Diodes + 1 EMI Filter + 1 Voltage Regulator + 1 LED Driver IC |
| Energy Storage | 2 x 100 µF Electrolytic Capacitors (35V) + 2 x 10 µF Tantalum (25V) |
| Operating Temperature | 0°C to +55°C (32°F to 131°F) |
| Storage Temperature | -25°C to +85°C (-13°F to 185°F) |
| Mounting Type | DIN Rail or MICREX-SX PLC Rack |
| Status Indicators | 16 Green LEDs (One per Channel) + 1 Green LED (Power) |
Input Channel Features and Signal Processing
The FUJI NP1X6406-W accepts sixteen independent discrete input signals at 24 VDC. Specifically, each input includes an optocoupler for complete electrical isolation from the logic side. In addition, the input impedance of 3.4 kΩ suits standard industrial proximity sensors. Moreover, all sixteen channels respond within 3 milliseconds to signal changes. Consequently, this module captures fast field events without missing critical transitions.
High-Density Input Configuration
Sixteen input channels fit into a single MICREX-SX rack slot with this module. For instance, you can monitor up to sixteen limit switches or push buttons with one module. In addition, the two common groups allow mixed sink and source wiring if needed. Moreover, the removable terminal block accepts 18-22 AWG stranded or solid wires. Therefore, this module saves valuable rack space in large control systems.
Energy Storage and Operational Stability
This digital input module stores energy using four onboard capacitors for power filtering. Specifically, two electrolytic capacitors smooth the 24 VDC supply for stable optocoupler operation. In addition, two tantalum capacitors provide high-frequency noise suppression for the input circuits. Furthermore, these capacitors maintain stable operation during brief power interruptions. Thus, the FUJI NP1X6406-W continues functioning through minor supply dips reliably.
Installation and Diagnostic Indicators
Seventeen LED indicators provide operational status at a glance on this module. First, sixteen green LEDs light when each corresponding input receives an active 24 VDC signal. Second, a green Power LED indicates the presence of backplane operating voltage. Additionally, the module includes a locking lever for secure rack attachment. Thus, you can diagnose system status instantly without external tools or meters.
MeloAuto-Trusted PLC & DCS Parts Supplier















WeChat
Scan the QR Code with wechat