Module Overview
This network module connects operator workstations to Bailey INFI 90 controllers. You can install ABB Bailey IIDOP04A directly into any VME rack slot of INFI 90 systems. The unit manages data exchange between the process control network and display stations. It formats plant data for easy operator visualization.
Technical Specifications
| Parameter | Value |
|---|---|
| Dimensions (W x H x D) | 233 mm x 160 mm x 20 mm |
| Weight | 0.52 kg |
| Network interface | 10/100Base-TX Ethernet (RJ-45) |
| Serial interface | RS-232/485 (9-pin D-sub) |
| Supported protocols | Bailey GOP, Modbus RTU, Modbus TCP |
| VMEbus interface | 32-bit master/slave |
| Maximum data rate | 100 Mbps Ethernet, 115.2 kbps serial |
| Data buffering | 2 MB SRAM |
| Configuration port | RS-232 (front panel) |
| Status indicators | 10 LEDs (network, power, comm status) |
| Power requirements | 5V DC at 1.5A from VME backplane |
| Total onboard components | 398 discrete parts |
| Energy storage type | Tantalum and electrolytic capacitors |
| Energy storage rating | 890 µF at 16V DC |
| Operating temperature | 0°C to +55°C |
Board Layout and Components
The PCB integrates dual communication processors for independent protocol handling. Two megabytes of SRAM buffer process data before network transmission. Moreover, 398 discrete components include memory controllers and bus interface logic. Tantalum capacitors filter noise on all processor power rails. Consequently, the module delivers clean data to operator displays without corruption.
Installation Process
You can mount ABB Bailey IIDOP04A into any standard VMEbus rack slot. The backplane connectors supply power and provide VMEbus access to controller data. Furthermore, front panel ports connect to Ethernet switches and serial devices. Configuration software sets communication parameters and data mapping easily.
Performance Advantages
This module translates between Bailey GOP protocol and standard Modbus formats. The dual-port design connects to both Ethernet and serial operator panels. Therefore, legacy workstations integrate with modern INFI 90 systems seamlessly. The 2 MB buffer also prevents data loss during peak network traffic.
Safety and Compliance
ABB Bailey IIDOP04A meets CE and RoHS industrial standards. The board discharges stored energy below 3V within eight seconds. Hence, technicians face minimal electrical risk during installation or replacement.