This module executes user logic and manages I/O for ABB S100 controllers. The ABB 3BSE000270R1 provides reliable processing for industrial automation applications. It measures 180 mm in width and 120 mm in height. This unit weighs approximately 0.50 kg for rack mounting.
Technical Specifications Table
| Parameter | Value |
|---|---|
| Product Model | ABB 3BSE000270R1 |
| Brand | ABB |
| Category | Processor Module / CPU |
| Compatible Series | ABB S100 / Advant |
| User Memory | 64 KB RAM (battery-backed) |
| Memory Technology | Static RAM with lithium battery |
| Processing Speed | 0.6 ms per 1K of bit operations |
| I/O Address Space | 1024 digital inputs + 1024 digital outputs |
| Timer/Counter Range | 128 timers, 128 counters |
| Dimensions (W x H x D) | 180 mm x 120 mm x 50 mm |
| Weight | 0.50 kg |
| Programming Port | 1 x 9-pin SUB-D (RS232) |
| Expansion Interface | 1 x 20-pin ribbon cable |
| Internal Components | 1 x 16-bit CPU, 1 x quartz oscillator |
| Energy Storage | 1 x 3.6 V lithium battery (0.8 Ah capacity) |
| Battery Life | Approximately 2 years |
| LED Indicators | 4 x status (Power, Run, Stop, Fault) |
| Operating Temperature | 0°C to 55°C |
Internal Architecture and Processing Power
This processor module uses a 16-bit CPU for logic execution. A quartz oscillator provides precise timing for all operations. The ABB 3BSE000270R1 stores user programs in 64 KB of static RAM. A replaceable lithium battery maintains this memory during power outages. The processor executes bit operations in approximately 0.6 milliseconds per kilobyte. Consequently, this module handles medium-sized applications reliably.
Installation and Programming Guide
First, insert this processor module into the designated slot of your S100 rack. Next, connect your programming device to the 9-pin RS232 port. Then, upload your application using ABB programming software. The module supports ladder diagram and function block languages. You can expand I/O by adding S100 remote racks via ribbon cable. This processor module communicates with I/O modules through the backplane bus. Four LED indicators show power, run, stop, and fault status. Always replace the lithium battery when the low voltage warning appears. Remove the module from the rack before changing the battery for safety.