Analog Output Expansion for S7-200 CN Systems
The Siemens 6ES7232-0HB22-0XA8 functions as an EM 232 analog output module for the SIMATIC S7-200 CN series, specifically designed for S7-22X CPUs . This module provides 2 analog output channels, each delivering a ±10 V DC signal with a 12-bit converter for voltage outputs and 11-bit for current outputs . Consequently, this module enables precise control of actuators, valves, and other analog devices in industrial processes. The module requires 70 mA from an external 24 V DC supply and 20 mA from the 5 V DC backplane bus . Its compact dimensions of 46 mm width, 80 mm height, and 62 mm depth make it suitable for space-constrained control panels .
Technical Specifications
| Specification | Value |
|---|---|
| Model | 6ES7232-0HB22-0XA8 |
| Product Type | EM 232 Analog Output Module |
| System Compatibility | S7-200 CN (S7-22X CPU only) |
| Analog Outputs | 2 |
| Output Voltage Range | ±10 V DC |
| Output Current Range | 4 mA to 20 mA |
| Resolution (Voltage) | 12 bits |
| Resolution (Current) | 11 bits |
| Settling Time (Voltage) | 100 µs |
| Settling Time (Current) | 2 ms |
| Current Consumption (24 V DC) | 70 mA (max.) |
| Current Consumption (5 V DC) | 20 mA (max.) |
| Power Loss | 2 W (typical) |
| Load Impedance (Voltage) | 5 kΩ (min.) |
| Load Impedance (Current) | 0.5 kΩ (max.) |
| Dimensions (W x H x D) | 46 mm x 80 mm x 62 mm |
| Weight | Approx. 0.129 kg |
| Approvals | CE only |
| Product Lifecycle | Discontinued (since 2021-10-01) |
Output Performance and Accuracy
The Siemens 6ES7232-0HB22-0XA8 delivers a settling time of 100 µs for voltage outputs and 2 ms for current outputs, ensuring rapid response to control signals . The module achieves a basic error limit of ±0.5% at 25 °C, with an operational error limit of ±2% across the full temperature range . It supports signal ranges from -32,000 to +32,000 and unipolar ranges from 0 to 32,000 for displayable conversion values . The module does not provide potential separation for analog outputs, so users must consider this in their system design . It also does not support plug-in I/O terminals .
Installation and Important Notes
The Siemens 6ES7232-0HB22-0XA8 mounts directly onto the S7-200 expansion bus, simplifying system integration. Please note that Siemens has discontinued this product effective October 1, 2021, and it is now available only as a spare part . This CN version carries CE approval only and is specifically intended for the Chinese market . For users requiring full international certifications, the standard version 6ES7232-0HB22-0XA0 may be more suitable.
MeloAuto-Trusted PLC & DCS Parts Supplier

















WeChat
Scan the QR Code with wechat