This output module drives eight AC loads from a TSX Compact PLC system. It switches 120 VAC power to solenoids, contactors, and indicator lights. You can rely on this unit for reliable control of industrial AC devices.
Technical Specifications
| Parameter | Value |
|---|---|
| Model | Schneider ASBDAP 102 |
| Category | Output Module 8 Point 120VAC |
| Number of Outputs | 8 points |
| Output Type | TRIAC (solid-state, AC switching) |
| Output Voltage Range | 85–132 VAC, 50/60 Hz |
| Output Current per Point | 0.5 Amps maximum |
| Maximum Load per Module | 4 Amps total |
| Inrush Current | 10 Amps for 1 cycle (non-repetitive) |
| OFF-State Leakage | 1.5 mA maximum at 120 VAC |
| Output Response Time | 1/2 cycle (8.3 ms at 60 Hz, 10 ms at 50 Hz) |
| Isolation | 2500 VAC optical (field to logic) |
| Internal Power Draw | 120 mA from +5 VDC backplane |
| Dimensions (W x H x D) | 3.8 cm × 12.0 cm × 10.5 cm |
| Weight | 0.32 kg (0.71 lbs) |
| Connector Type | One 20-pin removable terminal block |
| Component Count | 1 main board + 8 TRIACs + 8 optoisolators + 8 LEDs |
| Energy Storage | 100 µF buffer capacitor |
| Protection | Internal snubber network for each output |
Output Design and Switching
The Schneider ASBDAP 102 uses eight TRIAC solid-state switches for AC load control. Each output includes an internal snubber network for inductive load switching. The TRIAC turns on at zero voltage crossing and turns off at zero current. Consequently, this design reduces electrical noise and extends load contact life.
Performance Characteristics
Each output handles 0.5 Amps of continuous AC current at 120 VAC. The total module load should not exceed 4 Amps across all eight points. Inrush current up to 10 Amps for one cycle will not damage the TRIAC. The OFF-state leakage current of 1.5 mA will not energize most industrial loads.
Response Time and Coordination
The module responds within one-half cycle of the AC line frequency. At 60 Hz, response time equals 8.3 milliseconds maximum. At 50 Hz, response time equals 10 milliseconds maximum. Therefore, this speed works perfectly for machine control and process applications.
Isolation and Noise Immunity
Optical isolators separate each output channel from the logic side. This 2500 VAC rating prevents noise from corrupting the PLC backplane. The internal snubber also reduces radiated EMI from inductive loads. Consequently, you can mount this module near variable frequency drives without interference.
Installation and Wiring
Mount this module in any I/O slot of a TSX Compact rack. The 20-pin removable terminal block accepts wire sizes from 16 to 22 AWG. For best results, use copper conductors rated for 90°C minimum. You should also install external fuses rated at 1 Amp for each output channel.
Visual Status Indication
Eight red LEDs on the front panel show the real-time output status. Each LED illuminates when its corresponding TRIAC receives a turn-on signal. Therefore, technicians can verify output operation without a multimeter. A green LED indicates that the module has backplane power.
Why Choose This Output Module
This solid-state module outperforms relay outputs in high-cycle applications. It has no moving parts, so wear and tear do not exist. Therefore, this unit suits packaging machines, conveyors, and labeling equipment with frequent cycling.