Overview
The Honeywell 51410069-175 Analog Input Module, model CC-PAIN01, delivers precise signal acquisition for industrial control systems. It efficiently processes high-level current inputs from field transmitters and ensures consistent measurement accuracy. Built for reliability, the CC-PAIN01 provides non-incendive power, fast scan speed, and extensive self-diagnostics — ideal for demanding Class 1, Division 2 environments.
Key Features
- Supports 16 single-ended input channels for 2-wire or self-powered transmitters
- Offers non-incendive field power with individual current-limited protection
- Includes built-in self-diagnostics and optional redundancy for higher system reliability
- Provides fast 50 ms input scan rate for real-time control and monitoring
- Ensures high measurement precision with 16-bit A/D resolution
- Designed for hazardous area protection, meeting Division 2 non-incendive standards
Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Product Model | 51410069-175 / CC-PAIN01 |
| Input / Output Type | High-Level Analog Input |
| Associated IOTA Models | CC-TAIN01 (Non-Redundant, 6”) / CC-TAIN11 (Redundant, 12”) |
| Input Type | Current (2-wire or self-powered transmitters) |
| Number of Channels | 16 channels (single-ended) |
| Input Range | 4–20 mA (through 200 Ω) |
| A/D Converter Resolution | 16 bits |
| Scan Rate | 50 ms |
| Common Mode Rejection (0–60 Hz) | 70 dB |
| Normal Mode Rejection (60 Hz) | 20 dB |
| Filter Response | Single-pole RC, -3 dB @ 6.0 Hz |
| Maximum Input Voltage | ±30 V |
| Channel Crosstalk (0–60 Hz) | -60 dB |
| Accuracy (@23.5°C ±2°C) | ±0.075% of full scale |
| Accuracy (0–60°C) | ±0.15% of full scale |
| Field Power Conditioning | Individually protected, current-limited circuits; no fusing required |
| Environmental Rating | Class 1, Division 2 Non-Incendive |
| Redundancy Option | Supported via CC-TAIN11 IOTA |
Performance and Design
The Honeywell CC-PAIN01 uses a 16-bit A/D converter to achieve precise current-to-digital conversion. It minimizes noise and interference through strong rejection ratios and robust filtering. Each channel includes its own power-limiting circuit, ensuring continuous protection without external fuses. Engineers can combine CC-PAIN01 with CC-TAIN11 for redundancy or CC-TAIN01 for compact, non-redundant setups.
Applications
The 51410069-175 / CC-PAIN01 module is widely used in:
- Distributed Control Systems (DCS)
- Refining and chemical process automation
- Power generation plants and industrial monitoring systems
- High-precision measurement and control loops
Origin, Dimensions & Weight
- Brand: Honeywell
- Country of Origin: USA
- Module Width: 6″ (non-redundant) / 12″ (redundant)
- Approximate Weight: 0.6 kg