This GE DS200STBAG1A DS200STBAG1ADC Turbine Control Terminal Board provides screw terminal connections for turbine control signals. The board interfaces between field sensors and the Mark V control system. You will find this component in many GE turbine control cabinets globally. The DS200STBAG1ADC variant includes a rugged conformal coating for harsh environments.
Technical Specifications
| Parameter | Specification |
|---|---|
| Full Model | GE DS200STBAG1A DS200STBAG1ADC Turbine Control Terminal Board |
| Category | Turbine Control Terminal Board |
| Terminal Points | 100 Screw-Type Terminals |
| Maximum Voltage | 300 V AC or DC |
| Maximum Current | 10 A per Terminal |
| Wire Gauge | 26 AWG to 14 AWG |
| Isolation | 2500 V RMS between Groups |
| Dimensions (H x W) | 300 mm x 220 mm |
| Weight | Approximately 1.45 kg |
| Connectors | 3 x 50-Pin Ribbon Headers |
| Component Count | 32 Passive Components (Filters) |
| Energy Storage | None (Passive Board) |
Field Wiring and Signal Routing Features
The GE DS200STBAG1A DS200STBAG1ADC Turbine Control Terminal Board organizes critical turbine signals into functional groups. Each terminal includes a labeled position for easy identification during maintenance. The board routes signals directly to the 50-pin ribbon headers for controller connection. Furthermore, it includes RC filter networks on all analog inputs. Consequently, noise from long turbine field cables does not affect control accuracy.
Installation and Connection Steps
Mount this GE DS200STBAG1A DS200STBAG1ADC Turbine Control Terminal Board in the lower section of any Mark V cabinet. First, secure the board using four M4 mounting screws at the corners. After that, attach field wiring to the screw terminals following the printed labels. Then, connect the three ribbon cables to the corresponding controller boards. Finally, verify each connection before applying power to the turbine control system.
Energy Discharge and Safety Notice
This GE DS200STBAG1A DS200STBAG1ADC Turbine Control Terminal Board stores no significant energy. Therefore, you can handle it immediately after power removal. However, field wiring may carry hazardous voltages from external turbine sensors. Always disconnect external power before touching any terminal.
Status Indication and Diagnostics
This terminal board has no active indicators or LEDs. However, each terminal position includes a test point for meter connection. You can verify signal presence using these test points without removing wires. The clear labeling helps technicians identify turbine control channels quickly during troubleshooting.