This network alarm and display station provides operator interface capability for ABB Bailey INFI 90 systems. It displays alarms, process variables, and system status in real time. Therefore, it enables operators to monitor turbine and plant operations effectively.
Physical and Display Specifications
The ABB Bailey NADS02 measures 25.0 cm in length and 18.0 cm in width. Moreover, its station weight equals approximately 1.20 kg for panel mounting. A single 48-pin male connector links this station to the INFI 90 backplane. Additionally, the unit includes a graphical display and integrated alarm indicators.
| Parameter | Specification |
|---|---|
| Brand | ABB Bailey |
| Full Model | NADS02 |
| Category | Network Alarm and Display Station |
| Dimensions (L x W x H) | 25.0 cm x 18.0 cm x 6.5 cm (9.84″ x 7.09″ x 2.56″) |
| Station Weight | 1.20 kg (2.65 lbs) |
| Backplane Interface | 1 x 48-pin Male Connector (INFI 90 Rack) |
| Power Supply Input | 24 VDC from Backplane (19.2 to 28.8 VDC) |
| Power Consumption | 8 W (Typical) |
| Display Type | Monochrome LCD (Backlit) |
| Display Resolution | 240 x 128 Pixels (Graphical) |
| Display Size | 14.0 cm x 7.0 cm (5.51″ x 2.76″) |
| Text Display Capacity | 8 Lines x 40 Characters (Maximum) |
| Graphic Display Capacity | 240 x 128 Dot Graphics |
| Backlight Type | LED (Green/Yellow) |
| Backlight Life | 50,000 Hours (Minimum) |
| Alarm Indicators | 16 Red LEDs (High Priority) + 8 Yellow LEDs (Low Priority) |
| Audible Alarm | Internal Buzzer (Software Controllable) |
| Communication Ports | 1 x RS-232 (Local Programming) + 1 x RS-485 (Network) |
| Network Protocol | Bailey PC90 |
| Baud Rate | 19200 baud (Fixed for Network) |
| On-Board Components | 1 Microcontroller + 1 LCD Controller + 4 Memory Chips + 2 UARTs + 1 Display Driver + 8 Protection Diodes + 1 Voltage Regulator + 1 Isolation Transformer + 1 Buzzer Driver + 24 LED Drivers |
| Energy Storage | 3 x 470 µF Electrolytic Capacitors (35V) + 3 x 100 µF (16V) + 2 x 10 µF Tantalum (25V) |
| Isolation Rating | 1500 Vrms (Network Port to Logic) |
| Operating Temperature | 0°C to +55°C (32°F to 131°F) |
| Storage Temperature | -25°C to +85°C (-13°F to 185°F) |
| Protection Rating | IP54 (Front Panel) |
| Mounting Type | Panel Mount (Cutout 23.5 cm x 16.5 cm) |
| Status Indicators | 1 Green LED (Power) + 1 Green LED (Network Active) + 1 Red LED (System Fault) |
Display and Alarm Features
The ABB Bailey NADS02 features a graphical 240 x 128 pixel LCD display. Specifically, the screen shows process diagrams, alarm texts, and system status clearly. In addition, sixteen high-priority red LEDs alert operators to critical turbine conditions. Moreover, eight low-priority yellow LEDs indicate non-critical warnings and events. Furthermore, an internal buzzer provides audible notification for active alarms. Consequently, operators can respond to plant events quickly and effectively.
Network Communication and Integration
This alarm and display station connects to INFI 90 networks using Bailey PC90 protocol. For instance, the RS-485 port handles network communication at 19200 baud. In addition, the station receives real-time alarm and process data from the system controller. Moreover, the RS-232 port allows local configuration without network disruption. Thus, this station integrates seamlessly into existing INFI 90 installations.
Energy Storage and Operational Stability
This station stores energy using eight onboard capacitors for power filtering. Specifically, three electrolytic capacitors smooth the 24 VDC supply for stable LCD operation. In addition, three capacitors filter power for the backlight and alarm LEDs. Furthermore, two tantalum capacitors provide high-frequency noise suppression for logic circuits. Therefore, the ABB Bailey NADS02 continues operating through brief power interruptions reliably.
Installation and Diagnostic Indicators
Three LED indicators provide operational status at a glance on this station. First, a green Power LED lights when the 24 VDC supply is present. Second, a green Network Active LED flashes during data exchange with the system controller. Third, a red System Fault LED indicates hardware errors or network timeouts. Additionally, the station requires a panel cutout of 23.5 cm by 16.5 cm. Thus, this alarm station fits standard industrial enclosure openings perfectly.