Product Overview
The Honeywell FS-BSDOL-04UNI functions as a dedicated range-setting module for the SDOL-0424 loop-monitored output module within the Safety Manager SC system. This module sets precise current sensing thresholds across four independent output channels . Accordingly, the FS-BSDOL-04UNI prevents false lead-break detection on unused channels, ensuring reliable operation in safety-critical applications.
Technical Specifications
The FS-BSDOL-04UNI offers four load range settings labeled S, L, M, and H for flexible configuration . This module mounts directly on the programming connector of the I/O backplane without consuming additional chassis space . Furthermore, the module’s compact design simplifies installation while its modular construction permits customization through break-off sub-modules.
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Product Type | Range Setting Module |
| System Platform | Safety Manager SC / FSC |
| Supported Module | SDOL-0424 Loop-Monitored Output |
| Number of Channels | 4 |
| Load Range Settings | S: 4-16 mA; L: 17-47 mA; M: 48-199 mA; H: ≥200 mA |
| Power Requirement (S Setting) | 5 mA from 24 Vext of SDOL-0424 |
| Mounting Location | Programming connector (Px) on I/O backplane |
| Chassis Space Required | None |
| Module Dimensions | 58.5 × 54.5 × 12.5 mm |
| Sub-module Dimensions | 13.5 × 5.1 × 12.5 mm |
| Weight | Approx. 0.2 kg |
| Approvals | CE, TUV, UL, CSA, FM |
| Origin | USA |
Key Design Features
The FS-BSDOL-04UNI features a main section (BSDOL-04) that mounts on the programming connector of the I/O backplane . Additionally, the module includes sixteen range-setting sub-modules (four each for S, L, M, and H types) placed into four designated positions on the main section . This modular design provides straightforward customization for specific current load requirements. Moreover, the module’s high ±0.5% resolution accuracy ensures reliable current sensing and loop-monitoring performance .
Application and Integration
The FS-BSDOL-04UNI integrates seamlessly with Honeywell Safety Manager SC and FSC systems, supporting both 24V DC and 48V DC field load configurations . System engineers deploy this module in emergency shutdown (ESD) and safety instrumented systems (SIS) for precise output monitoring . Consequently, it plays a critical role in maintaining safety integrity in oil and gas, chemical processing, and power generation facilities.
MeloAuto-Trusted PLC & DCS Parts Supplier


















WeChat
Scan the QR Code with wechat