This module converts analog field signals to digital values for the controller. The GE IC200ALG432B accepts 4 voltage or current inputs for monitoring applications. It measures 110 mm in width and 85 mm in height. This unit weighs approximately 0.15 kg for DIN rail mounting.
Technical Specifications Table
| Parameter | Value |
|---|---|
| Product Model | GE IC200ALG432B |
| Brand | GE Fanuc / Emerson |
| Category | Analog Input Module |
| Compatible Series | VersaMax PLC |
| Number of Inputs | 4 differential channels |
| Input Types | Configurable per channel: 0-20 mA, 4-20 mA, 0-10 V, ±10 V |
| Resolution | 16 bits (32767 counts) |
| Accuracy | ±0.1% of full scale at 25°C |
| Update Rate | 10 ms per channel (40 ms all channels) |
| Input Impedance | 250 Ω (current), 100 kΩ (voltage) |
| Dimensions (W x H x D) | 110 mm x 85 mm x 55 mm |
| Weight | 0.15 kg |
| Connector Type | 1 x 12-pin removable terminal block |
| Internal Components | 1 x 16-bit ADC, 1 x multiplexer, 1 x microprocessor |
| Energy Storage | 4 x 0.1 µF input filtering capacitors |
| Electrical Isolation | 1500 V RMS between inputs and backplane |
| Overvoltage Protection | ±30 V DC continuous |
| Operating Voltage | 5 V DC (from backplane) |
| Power Consumption | 100 mA maximum |
| LED Indicators | 1 x status (OK) |
| Operating Temperature | 0°C to 60°C |
Internal Design and Analog Conversion
This analog input module uses a 16-bit ADC for precise signal conversion. A multiplexer scans all four channels sequentially for processing. The GE IC200ALG432B configures each channel independently for current or voltage. Four 0.1 µF capacitors filter high-frequency noise from input signals. An onboard microprocessor linearizes and scales the digital values. Consequently, this module delivers accurate analog readings for process control applications.
Installation and Wiring Guide
First, mount this module onto a standard 35 mm DIN rail securely. Next, wire your analog sensors to the input terminals (channels 1-4). Use shielded twisted-pair cables for all analog signal connections. Configure each channel’s input type using the VersaMax configuration software. The module provides a green LED for status indication. This analog input module works with all VersaMax PLC systems including IC200CPU series. Always connect the shield drain wire to earth ground for noise reduction.