Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

Honeywell C200/C300 Series/Honeywell/

Honeywell FS-TSFIRE-1624 Termination Assembly Module

Brand:Honeywell
Part Number:FS-TSFIRE-1624
Product: Termination Assembly Module
Origin:United States
Payment: T/T, Western Union
Price: USD 99
Dimensions: 170 × 70 × 58–64 mm
Weight: 0.16 kg
Warranty: 12 months

  • Product Details
  • Datasheet

Product Overview

The Honeywell FS-TSFIRE-1624 serves as a dedicated Field Termination Assembly (FTA) for fire detection applications within the Safety Manager and FSC (Fail-Safe Controller) safety systems . This module directly interfaces digital fire detectors and manual call points with the SAI-1620m high-density analog input module . Additionally, the FS-TSFIRE-1624 ensures reliable signal monitoring with comprehensive line supervision in safety-critical installations.

Technical Specifications

The FS-TSFIRE-1624 provides 16 supervised digital input channels for fire detectors . This module requires an external 24 V DC power supply and delivers a current-limited field signal for hazardous area compliance . Furthermore, the unit supports end-of-line (EOL) resistors to enable open-circuit and short-circuit supervision .

Parameter Specification
Manufacturer Honeywell
Number of Input Channels 16
Power Supply Voltage 24 V DC +25% / –15%
Max. Current Consumption 570 mA at 24 V DC ext.
No-Load Current Typ. 11 mA at 24 V DC
Channel Resistance 680 Ω ±5%
Short-Circuit Current 35 mA at 24 V DC ext.
Open Voltage (No Load) Typ. 23.5 V DC at 24 V DC ext.
Voltage with EOL Resistor Typ. 20.5 V DC at 24 V DC ext.
Relay Voltage Range 17 – 39 V DC
Relay Current Typ. 8.5 mA at 24 V DC
EOL Resistor (Recommended) 4.7 kΩ ±5%, 0.25 W
Field Wire Resistance Max < 100 Ω
Mounting DIN rail (TS32/TS35 × 7.5)
Used Rail Length 171 mm (6.73 in)
Module Dimensions (L×W×H) 170 × 70 × 58–64 mm
Weight 0.16–0.30 kg (varies by source)
Operating Temperature –20°C to +70°C
Approvals CE, TUV, UL, CSA, FM
Hazardous Location Class I, Division 2 certified
Origin USA

Key Design Features

The FS-TSFIRE-1624 provides power to each detector with voltage-current limitation in compliance with Class I Division 2 hazardous area requirements . This module includes a global reset function that removes supply voltage to all connected detectors via an onboard relay . Additionally, the unit uses an SICC-0001/Lx system interconnection cable to transmit the 16 input signals to a redundant pair of SAI-1620m modules for high availability . The screw-type terminals support wire sizes up to 2.5 mm² (AWG 14) with a tightening torque of 0.5 Nm, ensuring secure and serviceable field wiring .

Application and Integration

The FS-TSFIRE-1624 integrates seamlessly with Honeywell Safety Manager, FSC, and Experion PKS platforms in fire-and-gas (F&G) detection systems . System engineers commonly deploy this module in oil and gas refineries, chemical plants, and power generation facilities requiring SIL-rated fire monitoring . Consequently, it plays a vital role in emergency shutdown (ESD) and life safety applications where continuous, supervised fire detection is paramount .

Prev:

Next:

Chat Send Inquiry