This redundant controller provides high-availability processing for Honeywell SC S300 IOTA systems. The FC-TCNT11 maintains uninterrupted operation through automatic failover between dual processing units. Its redundant architecture eliminates single points of failure in mission-critical industrial applications. This controller supports seamless switchover without disrupting active process control loops.
Processing Capabilities and Memory Specifications
The FC-TCNT11 features a 32-bit RISC processor running at 200 MHz for fast execution cycles. This controller includes 8 MB of flash memory for firmware storage and 4 MB of RAM for data processing. The unit supports up to 512 I/O points per controller without any performance degradation. Additionally, the redundant pair synchronizes its execution cycles to ensure bumpless transfer during failover events.
| Parameter | Specification |
|---|---|
| Model Number | FC-TCNT11 |
| Product Type | SC S300 IOTA Redundant Controller |
| Processor | 32-bit RISC, 200 MHz |
| Flash Memory | 8 MB for firmware |
| RAM | 4 MB for operational data |
| Maximum I/O Points | 512 per controller |
| Redundancy Type | Active/Standby with auto failover |
| Switchover Time | Less than 50 milliseconds |
| Communication Ports | 2 x Ethernet, 1 x RS-485 |
| Diagnostics | Built-in self-test with health monitoring |
Physical Dimensions and Mounting Requirements
The FC-TCNT11 measures 180mm in width, 130mm in height, and 110mm in depth. This redundant controller weighs approximately 1.2 kilograms and mounts directly onto a standard DIN rail. The front panel provides LED indicators for power, status, and active/standby mode identification. Each unit includes a 50-pin backplane connector for interfacing with the IOTA system. Furthermore, the housing features a rugged metal construction that resists mechanical stress and vibration.
Energy Storage and Power Management
This controller consumes a maximum of 8.5 watts under full processing load. The FC-TCNT11 incorporates a supercapacitor-based energy storage system for data retention during power interruptions. This backup mechanism holds critical configuration data for up to 72 hours without external power. The unit also includes a real-time clock powered by a coin-cell battery for time-stamping events. Consequently, these features ensure data integrity and system reliability during unexpected power loss scenarios.
System Integration and Diagnostic Features
The FC-TCNT11 integrates seamlessly with Honeywell SC S300 IOTA distributed control systems. You can configure the controller using Honeywell’s engineering tools for streamlined setup and maintenance. The built-in diagnostic functions continuously monitor processor health, memory integrity, and communication status. Therefore, this redundant controller delivers exceptional availability for continuous process operations.