Overview
The Honeywell 900G01-0102 digital input module supplies 15VDC to external switching hardware, enabling contact closure detection. It features 16 single-ended inputs with galvanic isolation for reliable performance. LED indicators provide real-time status monitoring, and logic control allows state inversion when needed.
General Information
| Parameter | Details |
|---|---|
| Brand | Honeywell |
| Model | 900G01-0102 |
| Category | Digital Input Module |
| Input Type | Contact Closure |
| Inputs per Module | 16 (Single-Ended) |
Electrical Specifications
| Parameter | Details |
|---|---|
| Voltage Supplied | 15 VDC nominal (provided by controller) |
| Maximum Contact Resistance | 1000 ohms |
| Switching Current | 2.6 mA nominal |
| Galvanic Isolation | Isolation between field wiring and module (microcontroller or backplane) |
Response Time
| Parameter | Details |
|---|---|
| OFF to ON Response Time | 4 ms max |
| ON to OFF Response Time | 6 ms max |
* These values exclude controller scan time and transmission time from module to backplane.
Power Consumption
| Parameter | Details |
|---|---|
| 5V Power Supply Loading | 130 mA max |
| 24V Power Supply Loading | 40 mA max |
Status Indicators
| Indicator Type | Function |
|---|---|
| Green LED (Per Channel) | Indicates when a digital input is ON |
| Green Blinking LED | Shows that the module is being scanned |
| Amber Blinking LED | Highlights forced channels |
| Red LED | Signals a module diagnostics error |
MeloAuto-Trusted PLC & DCS Parts Supplier















WeChat
Scan the QR Code with wechat