This input block accepts analog current signals from field transmitters. It converts 4-20 mA loops into digital values for the Genius bus system. You can rely on this unit for precise process measurements in harsh industrial settings.
Technical Specifications
| Parameter | Value |
|---|---|
| Model | GE IC660EBA026 |
| Category | Current Source Input Block |
| Number of Inputs | 8 isolated channels |
| Input Signal Range | 4–20 mA (source type) |
| Input Impedance | 250 Ω per channel |
| Resolution | 12 bits (1 part in 4096) |
| Accuracy | ±0.1% of full scale at 25°C |
| Conversion Time | 10 ms per channel |
| Power Supply Required | 24 VDC ±10%, 150 mA |
| Field Loop Power | 24 VDC (block supplies it internally) |
| Dimensions (H x W x D) | 14.5 cm × 4.8 cm × 12.2 cm |
| Weight | 0.48 kg (1.06 lbs) |
| Connector Type | Two 18-pin removable terminal strips |
| Component Count | 1 logic board + 8 current sense resistors + 8 analog isolators + terminal blocks |
| Energy Storage | 330 µF input filter capacitor |
| Isolation | 2500 VAC (channel-to-bus) |
Input Design and Signal Processing
Each channel uses a precision 250 Ω resistor for current-to-voltage conversion. The GE IC660EBA026 provides loop power directly to 2-wire transmitters. You do not need an external power supply for your field devices. Moreover, the block buffers each input through an analog isolator for noise immunity.
Performance and Accuracy
This input block delivers 12-bit resolution across the entire 4-20 mA range. Its accuracy stays within ±0.1% under normal operating temperatures. Each channel converts its signal in just 10 milliseconds. Consequently, you can capture fast-changing process variables without missing critical data.
Installation and Wiring
Two removable terminal strips simplify field wiring connections significantly. You can wire each transmitter as a current source without worrying about ground loops. The block mounts directly onto a Genius I/O terminal base. For best results, use twisted-pair shielded cable for every analog input.
Energy Storage and Power Management
A 330 µF capacitor maintains stable voltage during momentary supply dips. The block draws only 150 mA from the 24 VDC bus. Meanwhile, it sources up to 40 mA of loop power per channel. This internal power capability reduces your panel’s component count.
Visual Status Indicators
Eight green LEDs show the active status of each analog channel. A single red LED indicates a loss of field power or an overrange condition. Therefore, technicians can identify faulty loops without opening the cabinet.
Why Choose This Block
This input block replaces older analog modules while using the same base wiring. Its sourcing capability works perfectly with 2-wire pressure and temperature transmitters. As a result, you will simplify your next control system retrofit project.
MeloAuto-Trusted PLC & DCS Parts Supplier


















WeChat
Scan the QR Code with wechat