Key Technical Specifications
This GE DS200ACNAG1ABB board operates from a 24V DC power supply. It provides Arcnet network communication at 2.5 Mbps speed. The unit measures 19 cm in length, 14 cm in width, and 3.5 cm in height. Its total weight equals 0.48 kg without any packaging materials.
The GE DS200ACNAG1ABB includes one coaxial Arcnet port for network cabling. Additionally, it features one 20-pin ribbon connector for host interface. A single 4-pin terminal block connects the DC power input. The board contains 1 Arcnet controller, 1 coaxial transceiver, 2 status LEDs, 1 isolation transformer, 10 resistors, and 8 capacitors.
| Parameter | Value |
|---|---|
| Power Supply | 24V DC ±10%, 120mA |
| Network Protocol | Arcnet (ANSI 878.1) |
| Data Rate | 2.5 Mbps |
| Network Topology | Bus or star |
| Dimensions (L x W x H) | 19 cm x 14 cm x 3.5 cm |
| Weight | 0.48 kg |
| Coaxial Port | 1 (BNC connector, 93 ohm) |
| Maximum Nodes | 255 per network |
| Maximum Cable Length | 300 meters per segment |
| Host Interface | 20-pin ribbon header |
| Power Connector | 4-pin terminal block |
| Arcnet Controller | 1 unit (COM20022) |
| Coaxial Transceiver | 1 unit |
| Status LEDs | 2 units (Power, Activity) |
| Isolation Transformer | 1 unit |
| Resistors | 10 units |
| Capacitors | 8 units |
| Energy Storage | 22 µF at 35V |
GE DS200ACNAG1ABB stores energy using one electrolytic capacitor. This capacitor provides 22 µF at 35V rating for transceiver hold-up. Consequently, the board maintains network connection during 10 millisecond power interruptions. Therefore, data packets remain intact through brief voltage dips.
Design and Integration
This board uses four-layer PCB construction with isolated coaxial interface for noise immunity. Consequently, the GE DS200ACNAG1ABB operates reliably from -10°C to +55°C ambient temperature.
For installation, you need M3 screws for the four mounting holes. The board draws 100 mA typical current from the 24V DC supply. The Arcnet network supports deterministic token-passing communication. We recommend using 93 ohm coaxial cable for all Arcnet connections.
Practical Application
This Arcnet communication board connects turbine and drive controls to legacy industrial networks. It transmits real-time data between multiple controllers in a deterministic manner. The GE DS200ACNAG1ABB also performs network initialization and node management. Therefore, it enables reliable distributed control for GE automation systems.
MeloAuto-Trusted PLC & DCS Parts Supplier