This isolated analog input module converts field sensor signals for ABB Bailey INFI 90 systems. It provides complete channel-to-channel isolation for critical process measurements. Therefore, it protects the control system from ground loops and electrical noise.
Physical and Input Specifications
The ABB Bailey 553087A1 measures 25.0 cm in length and 18.0 cm in width. Moreover, its module weight equals approximately 0.90 kg for rack mounting. A single 48-pin male connector links this module to the INFI 90 backplane. Additionally, the module provides four independently isolated analog input channels.
| Parameter | Specification |
|---|---|
| Brand | ABB Bailey |
| Full Model | 553087A1 |
| Category | Isolated Analog Input Module |
| Dimensions (L x W x H) | 25.0 cm x 18.0 cm x 5.5 cm (9.84″ x 7.09″ x 2.17″) |
| Module Weight | 0.90 kg (1.98 lbs) |
| Backplane Interface | 1 x 48-pin Male Connector (INFI 90 Rack) |
| Primary Interface | 1 x 16-pin Removable Screw Terminal Block |
| Operating Voltage | 24 VDC from Backplane (19.2 to 28.8 VDC) |
| Power Consumption | 5.0 W (Typical) |
| Analog Input Channels | 4 Isolated Channels |
| Input Signal Range (Voltage) | 0-10 VDC, -10 to +10 VDC, 0-5 VDC |
| Input Signal Range (Current) | 0-20 mA, 4-20 mA (with External Resistor) |
| Resolution | 14 Bits (0 to 16383 Counts) |
| Conversion Type | Sigma-Delta |
| Conversion Speed | 20 ms per Channel (80 ms for All 4 Channels) |
| Input Impedance (Voltage) | 1 MΩ (Typical) |
| Input Impedance (Current) | 250 Ω (with External Resistor) |
| Absolute Accuracy | ±0.2% of Full Scale at 25°C |
| Absolute Accuracy Drift | ±0.01% per °C |
| Channel Isolation | 1500 Vrms (Channel to Channel) |
| Isolation to Backplane | 1500 Vrms |
| Common Mode Rejection | 120 dB (50/60 Hz) |
| Normal Mode Rejection | 80 dB (50/60 Hz) |
| Common Mode Range | ±20 VDC Maximum |
| On-Board Components | 4 ADC Chips + 4 Signal Conditioning Circuits + 4 Isolation Transformers + 4 Protection Diodes + 1 EMI Filter + 1 Voltage Reference IC + 1 Microcontroller + 2 Memory Chips |
| Energy Storage | 4 x 100 µF Electrolytic Capacitors (35V) + 4 x 10 µF Tantalum (25V) |
| Operating Temperature | 0°C to +55°C (32°F to 131°F) |
| Storage Temperature | -25°C to +85°C (-13°F to 185°F) |
| Mounting Type | INFI 90 Rack (Single Slot) |
| Status Indicators | 1 Green LED (Power) + 1 Green LED (Active) + 1 Red LED (Fault) + 4 Green LEDs (Channel Valid) |
Isolated Input Features and Channel Separation
The ABB Bailey 553087A1 provides four independently isolated analog input channels. Specifically, each channel includes its own isolation transformer for complete electrical separation. In addition, the 1500 Vrms channel-to-channel isolation prevents ground loops between sensors. Moreover, the sigma-delta converter ensures excellent linearity and noise rejection for each channel. Furthermore, the 14-bit resolution delivers 16,383 discrete counts for precise measurement. Consequently, this module handles critical measurements where sensor grounds cannot be shared.
Signal Conditioning and Protection
Each isolated channel includes comprehensive signal conditioning for field sensors. For instance, built-in filters remove high-frequency noise from long field wiring. In addition, overvoltage protection clamps each input to safe levels during faults. Moreover, the 120 dB common mode rejection eliminates interference from nearby power equipment. Furthermore, you can configure each channel for voltage or current inputs with external resistors. Thus, the ABB Bailey 553087A1 provides reliable measurements in electrically noisy turbine environments.
Energy Storage and Isolation Integrity
This isolated input module stores energy using eight onboard capacitors for stable operation. Specifically, four electrolytic capacitors smooth the 24 VDC supply for all four channels. In addition, four tantalum capacitors provide high-frequency noise suppression for each ADC chip. Moreover, the isolation transformers prevent any DC path between channels or backplane. Furthermore, each channel’s power supply derives from isolated DC-DC converters. Therefore, this module maintains measurement integrity despite ground potential differences between sensors.
Installation and Diagnostic Indicators
Seven LED indicators provide operational status at a glance on this module. First, a green Power LED lights when the backplane supply voltages are present. Second, a green Active LED flashes during normal analog conversion operation. Third, a red Fault LED indicates hardware errors or out-of-range signals. Additionally, four green Channel Valid LEDs illuminate when each channel receives a valid signal. Furthermore, the module includes a locking ejector for secure backplane insertion. Thus, you can diagnose isolated input status instantly without external tools.
MeloAuto-Trusted PLC & DCS Parts Supplier















WeChat
Scan the QR Code with wechat