Function
The 8C-PAIHA1 Analog Input Module is designed to accept high-level current inputs from various transmitters and sensing devices. This module is particularly suited for applications requiring precise monitoring and control of process variables in industrial settings.
Notable Features
- Extensive Self-Diagnostics: Built-in diagnostic capabilities to ensure module integrity and functionality.
- Optional Redundancy: Enhances system reliability by providing backup capabilities.
- HART-Capable: Supports HART (Highway Addressable Remote Transducer) communication for multivariable devices, allowing for additional data exchange and diagnostics.
- Fast Loop Scan: Ensures quick response times for real-time monitoring.
- Field Power Selection: Offers flexibility with internal or external power options for field devices.
- Onboard Excitation Power: Eliminates the need for additional marshalling power, simplifying installation and maintenance.
- Galvanic Isolation: Provides safety and protection against electrical interference and surges.
Detailed Specifications
| Parameter | Specification |
|---|---|
| Module Type | 8C-PAIHA1 – Analog Input with HART (16), Coated |
| Input Type | Current (2-wire or self-powered transmitters) |
| Input Channels | 16 Channels (Single Ended type) |
| A/D Converter Resolution | 16 bits |
| Input Range | 4-20 mA (through 250 Ω) |
| Voltage Rating | 24 VDC |
| Module Current Rating | 110 mA |
| Common Mode Rejection Ratio | 70 dB (dc to 60 Hz with 500 Ω source imbalance) |
| Common Mode Voltage | -6 to +5 V peak (dc to 60 Hz) |
| Normal Mode Rejection Ratio | 19 dB (at 60 Hz) |
| Normal Mode Filter Response | Single-pole RC, -3 dB @ 6.5 Hz |
| Maximum Normal Mode Input | ± 30 Volts |
| Crosstalk | -60 dB (dc to 60 Hz channel-to-channel) |
| Maximum Input Voltage | ± 30 Volts (any input referenced to common, no damage) |
| Input Scan Rate | 50 ms |
| Hardware Accuracy | ± 0.075% of full-scale (23.5°± 2°C) ± 0.15% of full-scale (0 to 60°C) |
| Galvanic Isolation | 1000VAC RMS or ±1000 VDC |
| Isolation Technique | Icoupler (in IOM) |
| Module Removal and Insertion | Supported under power |
| Transmitter Field Power Conditioning | Individually protected current limiting circuits. No fuse required |
Notes:
- Note 1: No differential or voltage inputs are supported.
- Note 2: System-to-Field type isolation is available only with external user-supplied power.
MeloAuto-Trusted PLC & DCS Parts Supplier