This output module drives field loads from a Series 90-30 PLC system. It provides sixteen discrete outputs for controlling relays and solenoids. You will install this module in any I/O slot of the main rack.
Key Technical Specifications
The IC693MDL340E delivers sixteen positive-logic outputs at 12/24V DC. Each output channel handles up to 0.5A of continuous current. The module also includes a fused common for short-circuit protection.
| Parameter | Technical Data |
|---|---|
| Product Type | Series 90-30 Discrete Output Module |
| Output Channels | 16 positive-logic (sourcing) |
| Output Voltage Range | 12-24V DC |
| Output Current | 0.5A per channel maximum |
| Total Current | 4A per common (fused) |
| Response Time | 1 ms off-to-on, 1 ms on-to-off |
| Dimensions (W x H x D) | 2.5 cm x 13.6 cm x 12.7 cm |
| Total Weight | 0.28 kg (0.62 lbs) |
| Terminal Block | 1 x 20-position removable |
| Backplane Connector | 24-pin Series 90-30 interface |
| Onboard Fuses | 1 x 4A (user-replaceable) |
| Output Protection | Transient suppression diodes |
| LED Indicators | 16 green (one per channel) |
| Energy Storage | 100 µF decoupling capacitance |
| Operating Temperature | 0°C to 60°C |
Hardware Architecture and Output Driving
The IC693MDL340E uses sixteen MOSFET transistors for output switching. Each transistor includes a transient suppression diode across its terminals. One 4A fuse protects the entire common return path. Sixteen green LEDs light up when the corresponding output becomes active.
Interface and Connectivity
One 20-position removable terminal block connects output wiring to field devices. Each output channel shares a common return terminal group. A 24-pin backplane interface receives control commands from the CPU. You can replace the fuse without removing the module from the rack.
Practical Installation Notes
Install this output module in any I/O slot of a Series 90-30 rack. The IC693MDL340E requires an external 24V DC supply for output power. Always install a flyback diode across inductive loads like relays. Verify the total current per common does not exceed 4A for safe operation.