Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

Siemens Others/

Siemens 6ES7134-6HD00-0BA1 Analog Input Module for ET 200SP

Brand:Siemens
Part Number:6ES7134-6HD00-0BA1
Product:Analog Input Module
Origin:Germany
Payment: T/T, Western Union
Price: USD 99
Dimensions: 125mm x 75mm x 125mm
Weight: 0.8 kg
Warranty: 12 months

  • Product Details
  • Datasheet

Four-Channel Standard Analog Input with 2-Wire Connection

The 6ES7134-6HD00-0BA1 serves as a standard analog input module within the SIMATIC ET 200SP distributed I/O system. This module provides four analog input channels for 2-wire transducers and supports current signals from 0 to 20 mA and 4 to 20 mA. It offers 16-bit resolution, ensuring high-precision data acquisition for your automation tasks. Furthermore, the module supports configurable diagnostics per channel, enabling rapid fault detection and troubleshooting.

Technical Specifications

Parameter Specification
Manufacturer Siemens
Product Type Analog Input Module
Model AI 4xU/I 2-Wire ST
Series SIMATIC ET 200SP
Analog Inputs 4 differential inputs
Input Ranges 0-20 mA, 4-20 mA
Resolution 16 bits (including sign)
Input Resistance (4-20 mA) 280 Ω
Rated Load Voltage 24 V DC (19.2 to 28.8 V range)
Current Consumption (max.) 37 mA (without sensor supply)
Power Loss (typ.) 0.85 W (without sensor supply)
Destruction Limit (Input) 50 mA maximum
Address Space per Module 8 bytes + 1 byte QI information
Cable Length (shielded, max.) 800 m
Compatible BaseUnits BU type A0, A1
Dimensions (W x H x D) 15 mm x 73 mm x 58 mm
Weight (approx.) 0.035 kg

Operation and Installation

The 6ES7134-6HD00-0BA1 uses a 2-wire connection method, simplifying field wiring for current-based sensors. It supports both A0 and A1 BaseUnit types, providing flexibility for your system design. For 2-wire transmitters requiring loop power, connect the positive signal to the designated input terminal (e.g., pin 10) and the negative to the corresponding return terminal (e.g., pin 14). The module integrates smoothly with TIA Portal, starting from STEP 7 V11 SP2 or V13 for configuration .

Diagnostics and Configuration

This module provides configurable diagnostics for each channel, enabling precise fault isolation. Users can set interference frequency suppression to 50 Hz or 60 Hz to minimize AC noise on the signal. The module supports I&M identification data and allows firmware updates for feature enhancements. Furthermore, the compact 15 mm width makes it ideal for space-constrained control cabinets.