Core Function and System Role
The GE IS200TRPAS1A terminates analog field signals for Mark VI systems. Specifically, this board connects 4-20 mA transmitters to the controller. Moreover, it provides loop power for two-wire field devices. The IS200TRPAS1AFD variant includes conformal coating for harsh industrial environments.
Technical Specifications Overview
This terminal board features sixteen analog input channels. Each channel accepts 4-20 mA signals from field transmitters. Furthermore, the board provides 24 Vdc loop power for each channel.
| Parameter | Specification |
|---|---|
| Part Number | IS200TRPAS1A / IS200TRPAS1AFD |
| Type | Terminal Board / Analog Signal Termination |
| Analog Inputs | 16 Channels |
| Signal Type | 4-20 mA |
| Resolution | 14 Bits (16384 Counts) |
| Accuracy | ±0.2% of Span |
| Loop Power | 24 Vdc ±10%, 25 mA per Channel |
| Input Impedance | 250 Ω |
| Response Time | <50 ms |
| Status Indicators | 16 Green LEDs |
| Power Supply | 24 Vdc ±15% |
| Connector Types | 2 x 50-pin D-sub, 4 x Terminal Blocks |
| Dimensions (W x H x D) | 230 x 135 x 30 mm |
| Weight | 0.88 kg |
| Onboard Energy Storage | 8 x 100 µF, 35V Capacitors |
Connector Layout and Component Count
The board uses four terminal blocks for field wiring connections. For instance, block TB1 handles channels 1 through 4. Meanwhile, block TB2 manages channels 5 through 8. Blocks TB3 and TB4 handle channels 9 through 16. Two 50-pin D-sub connectors route analog signals to the controller. The IS200TRPAS1AFD adds a thick conformal coating over all components.
Energy Storage and Signal Integrity
This terminal board includes local capacitance for loop power filtering. Specifically, eight 100 µF capacitors stabilize the 24 Vdc supply. Therefore, the board provides clean power to field transmitters. Additionally, onboard LED indicators show each channel’s loop status. For example, a green LED illuminates when a valid 4-20 mA loop is active. An off LED indicates an open circuit or transmitter failure.
Diagnostic Features and Fault Detection
The board continuously checks each channel for open or shorted loops. Consequently, it detects transmitter failures within 100 milliseconds. Moreover, the GE IS200TRPAS1A IS200TRPAS1AFD includes loop current verification for each channel. This feature confirms that transmitters operate within the 4-20 mA range. An onboard status register reports all channel health to the main controller.
Maintenance and Hot Replacement
You can replace this terminal board without powering down the turbine. Thus, mean time to repair remains under ten minutes. The board stores no configuration data locally. Therefore, you simply install the replacement and resume normal analog termination.
Industrial Applications
This terminal board works inside GE Mark VI control cabinets. For reliable GE analog signal termination, the IS200TRPAS1A and IS200TRPAS1AFD deliver exceptional performance. They provide robust 4-20 mA interfacing for steam and gas turbine pressure and temperature transmitters.
MeloAuto-Trusted PLC & DCS Parts Supplier